Sizing of top plates

A couple of errors in the column headings for NZS 3604:2011 Timber-framed buildings Table 8.16 have left some scratching their heads. Here’s some pointers to get users back on track.

Topics include

Top & bottom plate
Sizing of top plates
Last updated 1 Oct 2014
Share

To correctly use NZS 3604:2011, it helps to first correct two column headings in Table 8.16(b):

● Change ‘Maximum spacing of trusses or rafters’ to ‘Maximum spacing of floor joists’.

● Maximum loaded dimension of wall’ should read ‘Maximum loaded dimension of wall supporting roof’.

Start with a question

What does the top plate support (see Figure 1)? This leads to the correct part of Table 8.16 to use:

● Where the top plate supports the rafters or trusses of a single or top storey – use Table 8.16(a).

● Where the top plate supports the mid-floor of 2 storeys – use Table 8.16(b).

● Where the top plate is part of a subfloor frame supporting a single storey – use Table 8.16(b).

● Where the top plate is part of a subfloor frame supporting 2 storeys – use Table 8.16(c).

a detailed diagram of various top plate options
Figure 1 Top plate options.

Other considerations

Limited substitution

Top plates can not be substituted with built-up members unless shown in Table 8.16. For example, where the table requires 90 × 70 mm, a built-up member of 2/90 × 35 mm is not permitted.

Positioned over studs

Table 8.16 doesn’t apply where rafters/trusses or floor joists are positioned directly over the studs below. In this situation, the top plate must be at least the same width as the studs and a minimum of 35 mm thick.

Bracing line maximum distance

Clause 8.7.4.2 requires a maximum distance of 5 m between bracing lines where the top plate is the boundary of a proposed ceiling and the ceiling is less than 600 kg/m3.

This can be extended up to 6 m when an additional 140 × 35 mm is added to the 90 × 45 mm top plate and fixed at 500 mm centres with either 2/100 × 3.75 mm hand-driven nails or 3/90 × 3.15 mm gun nails. This needs to be the same grade as the top plate.

Note: 10 mm standard plasterboard is about 700 kg/m3, so bracing lines up to 6 m would be allowed using the top plate options in Table 8.16,that is, 90 × 35 mm added to 90 × 45 mm.

Truss supports

Table 8.16 allows for some top plate selections to have a truss supported within 150 mm of the supporting studs. Alternatively, the truss/rafter can sit anywhere on the plate in relation to the studs. The following examples use ‘anywhere’.

Example 1 – Table 8.16(a)

The first example is for a single-storey or upper storey frame supporting a roof, so Table 8.16(a) is used. The parameters are:

● heavy roof

● 600 mm stud spacing

● truss position is anywhere

● truss spacing is 900 mm

● loaded dimension of wall is 6 m.

Using Table 8.16(a), work through the steps (see Figure 2):

● Step 1 – Select the relevant column by choosing:

• heavy roof

• 600 mm stud spacing column.

● Step 2 – Select the relevant row(s) by looking at:

• the truss position of anywhere

• 900 mm truss spacing

• checking if these provide a loaded dimension of 6 m in the column selected in step 1.

● Step 3 – Read off the required top plate size in the first two columns of the selected row.

In this case, a 90 × 45 mm top plate is required with a 90 × 45 mm dwang under the top plate at the position of trusses or rafters. See NZS 3604:2011 Figure 8.13 for dwang fixings.

Alternatively, consider studs at 400 mm centres. This would require a double 90 × 45 mm top plate or a 90 × 45 mm with an additional 90 × 35 mm plate attached (fixed as referenced above). This option would require the 90 × 35 mm to be replaced with a 140 × 35 mm added to the top plate when bracing lines at right angles to the wall exceed 5 m spacing or if the ceiling is less than the 600 kg/m³ (standard 10 mm plasterboard is approximately 700 kg/m³).

an image of table 8.16 top plates of loadbearing walls
Figure 2 Example 1 using NZS 3604:2011 Table 8.16(a). Provided by Standards New Zealand under licence 001106.

Example 2 – Table 8.16(b)

The second example is for the lower of 2 storeys supporting a mid-floor or a subfloor stud wall supporting one storey. The parameters are:

● heavy roof

● stud spacing is 600 mm centres

● loaded dimension of wall supporting floor is 2.4 m

● floor joists at 400 mm centres

● loaded dimension of 6 m for the wall above the floor that is supporting the roof.

Using Table 8.16(b), work through the steps (see Figure 3(a)):

● Step 1 – Select the relevant column by choosing:

• heavy roof

• 600 mm stud spacing column.

● Step 2 – Select the relevant row(s) by looking at:

• loaded dimension of the wall supporting the floor, i.e. 2.4 m or more – choose 3 m

• maximum floor joist spacing of 400 mm

• checking if these provide a loaded dimension of 6 m in the column selected in step 1.

● Step 3 – Read off the required top plate size in the first two columns of the selected row(s). In this case, three options are available:

• 90 × 45 mm plus 90 × 45 mm

• 90 × 70 mm

• 90 × 45 mm plus 90 × 35 mm (this can only be used if the bracing lines at right angles to the walls are at 5 m centres or less).

an image of table 8.16 top plates of loadbearing walls
Figure 3 (a) Example 2 using NZS 3604:2011 Table 8.16(b). (b) Example 3 using NZS 3604:2011 Table 8.16(c). Provided by Standards New Zealand under licence 001106.

Example 3 – Table 8.16(c)

In the final example, the top plate is in a subfloor wall supporting 2 storeys. The parameters are:

● heavy roof

● stud spacing is 400 mm centres

● loaded dimension of wall supporting the floor is 1.3 m

● joist spacing is 400 mm centres

● loaded dimension of wall supporting roof is 6 m.

Using Table 8.16(c), work through the steps (see Figure 3(b)):

● Step 1 – Select the relevant column by choosing:

• heavy roof

• 400 mm stud spacing column.

● Step 2 – Select the relevant row(s) by looking at:

• loaded dimension, i.e. 1.3 m or more – choose 1.5 m

• maximum floor joist spacing of 400 mm

• checking if these provide a loaded dimension of 6 m in the column selected in step 1.

● Step 3 – Read off the required top plate size in the first two columns of the selected row(s). In this case three options are available:

• 90 × 45 mm plus 90 × 45 mm

• 90 × 70 mm

• 90 × 45 mm plus 90 × 35 mm – this can be used as the bracing lines in subfloors are a maximum of 5 m centres and would therefore comply with the requirements of clause 8.7.4.2.